upsLoadOut	: red		: 90			: UPS load is very high.
upsLoadOut	: yellow	: 70			: UPS load is high.

upsBattStat	: red		: Battery low		: Battery time remaning is low.
upsBattStat	: yellow	: Unknown		: Battery status is unknown.

upsOutStat	: red		: Off|Bypass		: {upsOutStat} ({upsFailCause})
upsOutStat	: yellow	: On battery|Unknown|Sleeping|Rebooting	: {upsOutStat} ({upsFailCause})
upsOutStat	: green		: voltage

upsBattRep	: yellow	: replacing		: {upsBattRep}

upsFailCause	: red		: voltage|Brownout|Blackout : {upsOutStat}

upsSecsOnBatt	: red		: 300			: UPS on battery for {upsSecsOnBatt} seconds.
upsMinsRunTime	: red		: <15			: UPS has less that 15 minutes of runtime remaining.

upsVoltageIn	: red		: 135			: UPS input voltage is extremely high. ({upsVoltageIn})
upsVoltageIn	: yellow	: >127,<110		: UPS input voltage is abnormal ({upsVoltageIn})